Schneider LC1D09M7 AC Contactor | Industrial Motor Control Supplier | SIMPLYBUY
海报

Schneider LC1D09M7

Rated Current: Schneider Electric
Number of Poles: 3P
Coil Voltage: 220VAC
Utilization Category: AC-3, AC-1
Auxiliary Contacts: 1 NO + 1 NC
Mechanical Endurance: Up to 20 million cycles
Electrical Endurance: Up to 2 million cycles
Insulation Voltage: 690V
Control Voltage Range: 70%~120% Uc
Frequency: 50Hz/60Hz
Mounting: DIN rail or screw mounting

Product Description

The TeSys GV motor circuit breaker is a 3-pole (3P) device rated at 50A/690V, specifically designed for the protection of 3-phase motors ranging from 11-22kW at 400V.


Protection Features
As a multifunction circuit breaker, it offers both thermal magnetic protection and advanced motor protection features.
With a breaking capacity of Icu 50kA at 400V, it ensures reliable interruption of fault currents.


Control and Connection
The start-stop control is operated via a toggle switch, and connections are made using Everlink BTR screw terminals.


Thermal and Magnetic Protection
Thermal protection is adjustable via dials, allowing for a setting current (Ir) range of 20-50A and a selectable tripping class of either 10 or 20.
Magnetic protection is set at 17 In, providing robust short-circuit protection.


Advanced Protection Settings
Advanced motor protection features can be configured using a smartphone via wireless NFC technology. These include:

  • Short time delay protection (Isd) with a setting range of 5-13 times Ir

  • Phase unbalance and loss protection

  • Ground fault protection

  • Locked rotor (jam) protection

  • Long start protection


Expandability
The circuit breaker has internal locations for installing additional auxiliary contact blocks (OF, SD) and voltage trip units (MN, MX).
Externally, it can be equipped with 1 or 2 auxiliary SDx modules, enabling alarming and fault differentiation functions.


Certifications
Certified to multiple international standards, including IEC, UL, CSA, CCC, EAC, Marine, and ATEX.


Applications
The TeSys GV motor circuit breaker is a versatile and reliable solution for a wide range of industrial motor protection applications.

Standard Features

The Schneider LC1D09M7 AC contactor features:

  • Circuit/Motor Control: Switches power circuits and controls motors, suitable for frequent starts.
  • Adaptability: Operates in wide voltage/frequency ranges and harsh environments.
  • Modular Design: Customizable with auxiliary contacts for various control needs.
  • Reliability: High mechanical and electrical durability.
  • Versatile Use: Ideal for industrial, building, and power distribution applications.

Technical Specifications

Attribute NameAttribute Value
Range of ProductTeSys Deca
Product or Component TypeContactor
Device short nameLC1D
Contactor applicationMotor control
Resistive load
Utilisation categoryAC-4
AC-3
AC-1
AC-3e
Poles description3P
[Ue] rated operational voltagePower circuit <= 690 V AC 25...400 Hz
Power circuit <= 300 V DC
[Ie] rated operational current9 A (at <140 °F (60 °C)) at <= 440 V AC AC-3 for power circuit
25 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit
9 A (at <140 °F (60 °C)) at <= 440 V AC AC-3e for power circuit
[Uc] control circuit voltage220 V AC 50/60 Hz
Motor power kW2.2 kW at 220...230 V AC 50/60 Hz (AC-3)
4 kW at 380...400 V AC 50/60 Hz (AC-3)
4 kW at 415...440 V AC 50/60 Hz (AC-3)
5.5 kW at 500 V AC 50/60 Hz (AC-3)
5.5 kW at 660...690 V AC 50/60 Hz (AC-3)
2.2 kW at 400 V AC 50/60 Hz (AC-4)
2.2 kW at 220...230 V AC 50/60 Hz (AC-3e)
4 kW at 380...400 V AC 50/60 Hz (AC-3e)
4 kW at 415...440 V AC 50/60 Hz (AC-3e)
5.5 kW at 500 V AC 50/60 Hz (AC-3e)
5.5 kW at 660...690 V AC 50/60 Hz (AC-3e)
Maximum Horse Power Rating1 hp at 230/240 V AC 50/60 Hz for 1 phase motors
2 hp at 200/208 V AC 50/60 Hz for 3 phase motors
2 hp at 230/240 V AC 50/60 Hz for 3 phase motors
5 hp at 460/480 V AC 50/60 Hz for 3 phase motors
7.5 hp at 575/600 V AC 50/60 Hz for 3 phase motors
0.33 hp at 115 V AC 50/60 Hz for 1 phase motors
Compatibility codeLC1D
Pole contact composition3 NO
Protective coverWith
[Ith] conventional free air thermal current25 A (at 140 °F (60 °C)) for power circuit
10 A (at 140 °F (60 °C)) for signalling circuit
Irms rated making capacity250 A at 440 V for power circuit conforming to IEC 60947
140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
Rated breaking capacity250 A at 440 V for power circuit conforming to IEC 60947