Relé de Sobrecarga Térmica TeSys Deca Schneider Electric LRD4367 – 95…120A, Classe 10A, Proteção de Motor de 55kW @ 400V Fornecedor | SIMPLYBUY
海报

Schneider Electric LRD4367 TeSys Deca Relé de Sobrecarga Térmica – 95…120A, Classe 10A, Proteção de Motor 55kW @ 400V

Fabricante: Schneider Electric
Modelo: LRD4367
Tipo: Relé de sobrecarga térmica diferencial
Thermal Setting Range: 95…120 A
Aula de Viagem: Classe 10A
Potência do motor: 55 kW @ 400 V AC
Contatos auxiliares: 1 NÃO + 1 NC
Detecção de falhas de fase: Sim

Descrição do produto

The Schneider Electric LRD4367 is a differential thermal overload relay from the TeSys Deca range, designed for direct mounting on TeSys D contactors LC1D115 and LC1D150 to form a compact motor starter. It provides thermal protection with an adjustable setting range of 95…120 A and a tripping class of 10A conforming to IEC 60947-4-1, protecting three-phase motors up to 55 kW at 400 V. The relay features phase failure and load unbalance detection, with tripping occurring at 130% of the set current on two phases. It includes a manual test button, a reset button, and a manual/automatic reset selector, along with 1 NO + 1 NC trip auxiliary contacts and a flag indicator. Temperature compensated from -20…60 °C, it ensures stable protection accuracy across varying ambient conditions. Typical applications include industrial motor control, pumps, fans, and compressors in demanding environments.

Recursos padrão

  • Adjustable Thermal Protection Range: Setting range of 95…120 A allows precise matching to the motor’s full-load current for reliable overload protection.
  • Característica de disparo da Classe 10A: Conforms to IEC 60947-4-1, providing standard trip times suitable for most industrial motor starting applications.
  • Phase Failure and Unbalance Detection: Differential mechanism trips at 130% of the set current on two phases, preventing motor damage from supply imbalance.
  • Direct Mounting on TeSys D Contactors: Mounts directly on the bottom terminals of LC1D115 and LC1D150 contactors to form a compact starter without additional wiring.
  • Reinicialização manual e automática: Includes test and reset buttons plus a selector for manual or automatic reset, with a trip flag indicator for clear status identification.
  • Temperature Compensated: Maintains accurate protection across an operating temperature range of -20…60 °C without derating.
  • Aprovações globais: Multi-standards certified to IEC, UL, CSA, CCC, EAC, and Marine standards, suitable for worldwide industrial applications.

Especificações técnicas

ParâmetroValor
FabricanteSchneider Electric
ModeloLRD4367
SérieTeSys LRD / TeSys Deca
Tipo de produtoRelé de sobrecarga térmica diferencial
Faixa de Ajuste de Proteção Térmica95…120 A
Aula de ViagemClasse 10A (IEC 60947-4-1)
Motor Power (AC-3 @ 400 V)55 kW
Tensão de isolamento nominal (Ui)1000 V (power circuit, IEC 60947-4-1)
Contatos Auxiliares1 NÃO + 1 NC
Sensibilidade à Falha de FaseTripping at 130% of Ir on two phases
Compensação de Temperatura-20…60 °C
PadrõesEN/IEC 60947-4-1, EN/IEC 60947-5-1, UL 60947-4-1, CSA C22.2 No 60947-4-1

Obter uma cotação

    ✕

    Obter uma cotação

      ✕

      Baixar catálogo