Disjuntor Motor Manual ABB MS116‑10 – 10A, 3 Polos, 4kW @ 400V (AC‑3), Classe 10A, Largura 45mm

Fabricante: ABB
Modelo: MS116-10
Tipo: Manual Motor Starter
Intervalo de configuração: 6.3…10 A
Potência do motor: 4 kW @ 400 V AC
Capacidade de interrupção: 50 kA @ 400 V AC
Classe de viagem: Classe 10A

Descrição do produto

The ABB MS116-10 is a compact three-pole manual motor starter from the MS116 series, designed for manual switching and fuseless protection of motors against short-circuits, overload and phase failures. It features an adjustable thermal overload release with a setting range of 6.3…10 A and a fixed magnetic short-circuit release set at 150 A. The device delivers a rated service short-circuit breaking capacity (Ics) of 50 kA at 400 V AC and a rated ultimate short-circuit breaking capacity (Icu) of 75 kA at 400 V AC, ensuring reliable fault interruption. With a trip class of 10A and temperature compensation from -25…+55 °C, it provides stable and accurate protection across varying ambient conditions. Its 45 mm width and DIN rail mounting make it ideal for space-efficient panel integration in industrial and commercial motor control applications.

Recursos padrão

  • Adjustable Thermal Overload Protection: Setting range of 6.3…10 A allows precise matching to the motor’s full-load current for reliable overload protection.
  • Fixed Magnetic Short-Circuit Protection: Short-circuit release set at 150 A ensures fast and dependable fault clearing.
  • High Short-Circuit Breaking Capacity: Rated service breaking capacity (Ics) of 50 kA at 400 V AC and ultimate breaking capacity (Icu) of 75 kA at 400 V AC provide robust protection.
  • Característica de disparo da Classe 10A: Conforms to IEC 60947-4-1, providing standard trip times suitable for most industrial motor starting applications.
  • Sensibilidade à falha de fase: Detects phase loss to prevent motor damage from unbalanced supply conditions.
  • Compensação de temperatura: Maintains accurate protection across an operating temperature range of -25…+55 °C without derating.
  • Fuseless Motor Protection: Eliminates the need for separate fuses, saving panel space and reducing wiring complexity.

Especificações técnicas

ParâmetroValor
FabricanteABB
ModeloMS116-10
Número do pedido1SAM250000R1010
Tipo de produtoManual Motor Starter (Motor Protection Circuit Breaker)
Setting Range (Overload)6.3…10 A (adjustable)
Magnetic Short-Circuit Release150 A (fixed)
Corrente operacional nominal (Ie)10.0 A
Tensão operacional nominal (Ue)690 V CA
Motor Power (AC-3)4 kW at 400/415 V AC
Capacidade de interrupção de curto-circuitoIcu: 75 kA at 400 V AC; Ics: 50 kA at 400 V AC
Classe de viagemClasse 10A (IEC 60947-4-1)
Dimensões (L × A × P)45 mm × 90 mm × 85.6 mm
Grau de proteçãoIP20
PadrõesIEC/EN 60947-1, IEC/EN 60947-2, IEC/EN 60947-4-1, UL 508, CSA C22.2