{"id":8971,"date":"2026-10-19T17:30:00","date_gmt":"2026-10-19T17:30:00","guid":{"rendered":"https:\/\/www.simplybuyglobal.com\/?p=8971"},"modified":"2026-11-05T08:59:40","modified_gmt":"2026-11-05T08:59:40","slug":"motor-starter-wiring-diagram","status":"publish","type":"post","link":"https:\/\/www.simplybuyglobal.com\/fa\/blog\/motor-control\/motor-starter\/motor-starter-wiring-diagram\/","title":{"rendered":"Motor Starter Wiring Diagram: Three-Phase Control, Overload and Stop Circuits"},"content":{"rendered":"<style id=\"wp-draft-card-style\">      .hero-card {       display: flex;       flex-wrap: wrap;       align-items: center;       background: #f7f8fa;       border-radius: 16px;       box-shadow: 0 6px 20px rgba(0, 0, 0, 0.05);       padding: 24px;       max-width: 700px;       margin: 35px auto;       font-family: Arial, sans-serif;       text-decoration: none;       color: inherit;  font-family: 'Poppins';     }      .hero-image {       width: 220px;       height: auto;       border-radius: 12px;       object-fit: cover;       flex-shrink: 0;     }      .hero-content {       padding-left: 24px;       flex: 1;       min-width: 260px;     }      .hero-title {       font-size: 1.6rem;       font-weight: bold;       margin-bottom: 12px;       color: #222;       font-family: 'Poppins', Arial, sans-serif;     }      .hero-description {       font-size: 1rem;       color: #555;       margin-bottom: 18px;     }      .hero-link {       display: inline-block;       padding: 10px 20px;       background-color: #0066cc;       color: #fff;       text-decoration: none;       border-radius: 8px;       font-weight: bold;       transition: background 0.2s ease-in-out;     }      .hero-link:hover {       background-color: #004c99;     }      @media (max-width: 640px) {       .hero-card {         flex-direction: column;         text-align: center;       }        .hero-content {         padding-left: 0;         padding-top: 20px;       }        .hero-image {         width: 100%;         max-width: 280px;       }     }    <\/style>\n\n\n\n<p class=\"wp-block-paragraph\"><strong>\u06f1\u06f6. \u067e\u0627\u0633\u062e \u0633\u0631\u06cc\u0639:<\/strong> A three-phase motor starter wiring diagram shows two circuits. The power circuit takes L1, L2 and L3 through a contactor and overload relay to the motor. The control circuit energizes the contactor coil through a normally closed stop chain, a start button and a parallel holding contact; the overload trip contact opens that chain. Always follow the drawing for the exact model. SIMPLYBUY helps buyers match starters, overloads and coil voltages across brands before quoting for your order.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">This guide explains the drawing for buyers and panel builders. You will learn how power and control paths work, why Start can be released after starting, where overload and stop contacts belong, and what to verify before buying a replacement. Follow the exact manufacturer instructions for installation and use a qualified electrician for live work.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">What Does a Three-Phase Motor Starter Wiring Diagram Show?<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">Most diagrams separate the power circuit, which carries motor current, from the control circuit, which energizes the contactor coil. A direct-on-line (DOL) starter is the simplest example: it connects the motor directly through a contactor and overload relay.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">The drawing may also show short-circuit protection, a control transformer, terminal numbers and a PLC interface. Read from supply to motor, then trace the control path separately. The <a href=\"https:\/\/www.simplybuyglobal.com\/fa\/product-category\/motor-control\/motor-starter\/\" rel=\"noopener noreferrer\" target=\"_blank\">motor starter range<\/a> includes assembled, modular and component-based types, and their drawings differ.<\/p>\n\n\n\n<h3 class=\"wp-block-heading\">Which Parts Form the Power Circuit?<\/h3>\n\n\n\n<p class=\"wp-block-paragraph\">Power runs from the three-phase supply through fuses, a breaker or motor protection, then the contactor, overload relay and motor. The contactor is the heavy-duty switch. The overload relay trips on sustained excess current but does not replace short-circuit protection.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Common IEC-style terminals are L1, L2 and L3 on the incoming side, and T1, T2 and T3 on the motor side. Some drawings use 1\/L1, 3\/L2 and 5\/L3 for the contactor input, and 2\/T1, 4\/T2 and 6\/T3 for its output.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">A compact starter can combine these parts. The <a href=\"https:\/\/www.simplybuyglobal.com\/fa\/product\/siemens-sirius-3ra6120-1bp32-compact-dol-motor-starter-0-32-1-25a-110-240v-ac-dc-690v\/\" rel=\"noopener noreferrer\" target=\"_blank\">Siemens SIRIUS 3RA6120-1BP32<\/a> has a 0.32\u20131.25 A setting range with integrated overload and short-circuit protection. Its terminal layout and control supply still must match the exact catalog number.<\/p>\n\n\n\n<div class=\"hero-card-wrapper\" data-wp-draft-card=\"1\"><a class=\"hero-card\" data-wp-card-role=\"button\" href=\"https:\/\/www.simplybuyglobal.com\/fa\/product\/siemens-sirius-3ra6120-1bp32-compact-dol-motor-starter-0-32-1-25a-110-240v-ac-dc-690v\/\" rel=\"noopener noreferrer\" target=\"_blank\"><img decoding=\"async\" alt=\"\u897f\u95e8\u5b50 SIRIUS 3RA6120 \u7535\u673a\u8d77\u52a8\u5668\uff0c\u7070\u8272\u5916\u58f3\uff0c\u5e26\u65cb\u94ae\u3001\u590d\u4f4d\u6309\u94ae\u548c\u63a5\u7ebf\u7aef\u5b50\uff0c\u4e0b\u65b9\u6709\u84dd\u7eff\u8272 SIEMENS \u6807\u5fd7\u3002\" class=\"hero-image\" data-wp-card-role=\"image\" src=\"https:\/\/www.simplybuyglobal.com\/wp-content\/uploads\/2026\/08\/3-56-scaled.jpg\"><div class=\"hero-content\"><div class=\"hero-title\" data-wp-card-role=\"title\">\u0631\u0627\u0647 \u0627\u0646\u062f\u0627\u0632 \u0645\u0648\u062a\u0648\u0631 DOL \u06a9\u0627\u0645\u067e\u06a9\u062a \u0632\u06cc\u0645\u0646\u0633 SIRIUS 3RA6120-1BP32 \u0628\u0627 \u062c\u0631\u06cc\u0627\u0646 \u0645\u062a\u0646\u0627\u0648\u0628\/\u0645\u0633\u062a\u0642\u06cc\u0645 0.32 \u062a\u0627 1.25 \u0622\u0645\u067e\u0631\u060c \u0648\u0644\u062a\u0627\u0698 110 \u062a\u0627 240 \u0648\u0644\u062a\u060c \u0648\u0644\u062a\u0627\u0698 690 \u0648\u0644\u062a<\/div><div class=\"hero-description\" data-wp-card-role=\"description\"><\/div><span class=\"hero-link\">\u0645\u0634\u0627\u0647\u062f\u0647 \u062c\u0632\u0626\u06cc\u0627\u062a \u0645\u062d\u0635\u0648\u0644<\/span><\/div><\/a><\/div>\n\n\n<h3>Which Parts Form the Control Circuit?<\/h3>\n<p>The control circuit begins at its own supply, often 24 V DC, 110 V AC or 230 V AC, and passes through the stop contacts, start button and contactor coil. The coil voltage must match that supply. It is separate from motor voltage, so a 400 V starter can have a 24 V DC coil.<\/p>\n<p>Protect the control supply as the panel design requires. A transformer may step line voltage down to coil voltage. Keep control and power wiring separated. For coil types, see <a href=\"https:\/\/www.simplybuyglobal.com\/fa\/blog\/motor-control\/ac-contactor\/understanding-ac-contactor-coil\/\" rel=\"noopener noreferrer\" target=\"_blank\">how a contactor coil works<\/a>.<\/p>\n<p><img loading=\"lazy\" decoding=\"async\" width=\"1600\" height=\"900\" alt=\"\u4ece\u53f3\u81f3\u5de6\u5c55\u793a\u7535\u673a\u542f\u52a8\u7535\u8def\uff1aABB MS116 \u624b\u52a8\u7535\u673a\u4fdd\u62a4\u5668\u3001\u65bd\u8010\u5fb7 LC1D65A \u63a5\u89e6\u5668\u548c\u4e00\u53f0\u4e09\u76f8\u7535\u673a\uff0c\u4e0a\u65b9\u5206\u522b\u6807\u6ce8 Protection\u3001Contactor \u548c Motor\u3002\" class=\"wp-image-8969\" src=\"https:\/\/www.simplybuyglobal.com\/wp-content\/uploads\/2026\/10\/inline-1-5.webp\" srcset=\"https:\/\/www.simplybuyglobal.com\/wp-content\/uploads\/2026\/10\/inline-1-5.webp 1600w, https:\/\/www.simplybuyglobal.com\/wp-content\/uploads\/2026\/10\/inline-1-5-500x281.webp 500w, https:\/\/www.simplybuyglobal.com\/wp-content\/uploads\/2026\/10\/inline-1-5-1200x675.webp 1200w, https:\/\/www.simplybuyglobal.com\/wp-content\/uploads\/2026\/10\/inline-1-5-300x169.webp 300w, https:\/\/www.simplybuyglobal.com\/wp-content\/uploads\/2026\/10\/inline-1-5-768x432.webp 768w, https:\/\/www.simplybuyglobal.com\/wp-content\/uploads\/2026\/10\/inline-1-5-1536x864.webp 1536w, https:\/\/www.simplybuyglobal.com\/wp-content\/uploads\/2026\/10\/inline-1-5-18x10.webp 18w, https:\/\/www.simplybuyglobal.com\/wp-content\/uploads\/2026\/10\/inline-1-5-133x75.webp 133w, https:\/\/www.simplybuyglobal.com\/wp-content\/uploads\/2026\/10\/inline-1-5-960x540.webp 960w, https:\/\/www.simplybuyglobal.com\/wp-content\/uploads\/2026\/10\/inline-1-5-480x270.webp 480w, https:\/\/www.simplybuyglobal.com\/wp-content\/uploads\/2026\/10\/inline-1-5-800x450.webp 800w\" sizes=\"auto, (max-width:767px) 480px, (max-width:1600px) 100vw, 1600px\" \/><\/p>\n<h2>How Does a Start-Stop Circuit Hold the Contactor In?<\/h2>\n<p>A typical three-wire control circuit follows this sequence:<\/p>\n<p><code>control supply \u2192 NC stop chain \u2192 NC overload contact \u2192 start button \u2192 coil A1 \u2192 A2 \u2192 neutral or 0 V<\/code><\/p>\n<p>A normally open (NO) auxiliary contact, often 13 and 14, is wired in parallel with Start. Press Start: the coil energizes, the main contacts and auxiliary contact close, and the auxiliary path holds the coil in after Start is released.<\/p>\n<p>Press Stop: its normally closed (NC) contact opens, the coil drops out and the motor stops. The holding contact opens too, so a new Start command is required.<\/p>\n<p>A PLC can perform the logic, but stop and safety functions must follow the risk assessment and local rules. See the <a href=\"https:\/\/www.simplybuyglobal.com\/fa\/blog\/motor-control\/motor-starter\/motor-starter-contactor-guide\/\" rel=\"noopener noreferrer\" target=\"_blank\">motor starter and contactor guide<\/a>.<\/p>\n<h3>What Opens the Circuit When the Motor Overloads?<\/h3>\n<p>A thermal overload uses bimetallic elements; an electronic overload uses current sensing. Sustained excess current trips the mechanism, opening its NC trip contact, commonly 95 and 96. The coil drops out and the motor stops.<\/p>\n<p>Set the relay to the motor&#8217;s full-load current using the manufacturer&#8217;s table. Trip class, ambient temperature and service factor affect the selection; <a href=\"https:\/\/www.simplybuyglobal.com\/fa\/blog\/motor-control\/overload-relay\/how-to-calculate-overload-relay-size\/\" rel=\"noopener noreferrer\" target=\"_blank\">how to size an overload relay<\/a> explains the range.<\/p>\n<p>A manual reset is typical. Auto-reset may restart the motor without warning, so the control design must prevent unexpected starting. Browse the <a href=\"https:\/\/www.simplybuyglobal.com\/fa\/product-category\/motor-control\/overload-relay\/\" rel=\"noopener noreferrer\" target=\"_blank\">overload relay category<\/a>.<\/p>\n<h3>Where Does an Emergency Stop Fit?<\/h3>\n<p>An emergency stop is a normally closed contact in the stop chain. It should not depend only on software. Depending on the risk assessment, it may operate a safety relay, contactor or dedicated safety circuit. It must stop the hazardous motion required by the safety design, not just switch off one motor.<\/p>\n<p>Keep stop contacts in series. A loose wire, damaged button or open overload should break the coil circuit. Never bypass a stop or overload to keep production running.<\/p>\n<h2>What Do the Terminal Labels Mean?<\/h2>\n<p>| Common label | Function | What to check |<\/p>\n<p>| &#8212; | &#8212; | &#8212; |<\/p>\n<p>| L1, L2, L3 | Three-phase line supply | Supply voltage and phase sequence |<\/p>\n<p>| T1, T2, T3 | Motor-side output | Cable and motor terminal match |<\/p>\n<p>| A1, A2 | Contactor coil supply | Coil voltage and control circuit |<\/p>\n<p>| 13, 14 | NO auxiliary contact | Holding, interlock or feedback |<\/p>\n<p>| 95, 96 | NC overload trip contact | Opens the coil circuit on trip |<\/p>\n<p>These labels are conventions, not universal instructions. Other brands may use another layout or hide internal links in the device manual. Trace the drawing for the exact catalog number.<\/p>\n<p><img loading=\"lazy\" decoding=\"async\" width=\"1500\" height=\"1000\" alt=\"Infographic titled Control Circuit Checks listing coil supply A1\/A2, auxiliary feedback NO\/NC and overload trip separate protection device beside a Schneider Electric TeSys LC1D65A contactor.\" class=\"wp-image-8970\" src=\"https:\/\/www.simplybuyglobal.com\/wp-content\/uploads\/2026\/10\/inline-2-5.webp\" srcset=\"https:\/\/www.simplybuyglobal.com\/wp-content\/uploads\/2026\/10\/inline-2-5.webp 1500w, https:\/\/www.simplybuyglobal.com\/wp-content\/uploads\/2026\/10\/inline-2-5-500x333.webp 500w, https:\/\/www.simplybuyglobal.com\/wp-content\/uploads\/2026\/10\/inline-2-5-1200x800.webp 1200w, https:\/\/www.simplybuyglobal.com\/wp-content\/uploads\/2026\/10\/inline-2-5-300x200.webp 300w, https:\/\/www.simplybuyglobal.com\/wp-content\/uploads\/2026\/10\/inline-2-5-768x512.webp 768w, https:\/\/www.simplybuyglobal.com\/wp-content\/uploads\/2026\/10\/inline-2-5-18x12.webp 18w, https:\/\/www.simplybuyglobal.com\/wp-content\/uploads\/2026\/10\/inline-2-5-113x75.webp 113w, https:\/\/www.simplybuyglobal.com\/wp-content\/uploads\/2026\/10\/inline-2-5-960x640.webp 960w, https:\/\/www.simplybuyglobal.com\/wp-content\/uploads\/2026\/10\/inline-2-5-480x320.webp 480w, https:\/\/www.simplybuyglobal.com\/wp-content\/uploads\/2026\/10\/inline-2-5-800x533.webp 800w\" sizes=\"auto, (max-width:767px) 480px, (max-width:1500px) 100vw, 1500px\" \/><\/p>\n<h2>Why Does the Starter Hum, Trip or Fail to Start?<\/h2>\n<h3>Why will the contactor not pull in?<\/h3>\n<p>Check the control fuse or breaker, every stop contact, the overload reset and the coil voltage. A stop button wired NO instead of NC, a loose wire or a PLC output unable to drive the coil will prevent operation. A damaged coil or wrong voltage can also be the cause.<\/p>\n<h3>Why must the start button be held?<\/h3>\n<p>The holding contact may be missing, wrongly placed or the wrong NO\/NC version. It must be parallel to Start and close with the contactor. A broken wire to that auxiliary contact produces the same symptom.<\/p>\n<h3>Why does the overload trip?<\/h3>\n<p>A setting below actual current, phase imbalance, mechanical overload, a hot panel or a faulty motor can cause a trip. A short circuit or ground fault needs testing, not repeated resetting. If the starter hums, chatters or overheats, isolate it and use the <a href=\"https:\/\/www.simplybuyglobal.com\/fa\/blog\/motor-control\/ac-contactor\/ac-contactor-failure-symptoms\/\" rel=\"noopener noreferrer\" target=\"_blank\">contactor failure symptoms guide<\/a>.<\/p>\n<h2>What Should You Check Before Ordering a Starter?<\/h2>\n<p>Collect the full starter code, motor nameplate and control drawing. Record full-load current, line voltage, phase, coil voltage and required terminals. Confirm overload range, auxiliary contacts, enclosure and short-circuit coordination.<\/p>\n<p>For a replacement, compare terminal layout and every auxiliary contact, not just current. Similar starters can differ in coil, trip class, reset method or integrated protection.<\/p>\n<p>Overload and short-circuit protection are separate jobs; the <a href=\"https:\/\/www.simplybuyglobal.com\/fa\/blog\/motor-control\/overload-relay\/overload-relay-vs-circuit-breaker\/\" rel=\"noopener noreferrer\" target=\"_blank\">overload versus circuit breaker guide<\/a> explains why.<\/p>\n<p>SIMPLYBUY is a multibrand distributor and supply-chain integrator, not a manufacturer. Send a nameplate, starter model and wiring requirement for a BOM review; the team can compare starters, contactors and overloads across brands. Confirm availability, documents and delivery terms through <a href=\"https:\/\/www.simplybuyglobal.com\/fa\/service\/\" rel=\"noopener noreferrer\" target=\"_blank\">sourcing support<\/a>.<\/p>\n<h2>What Do Buyers Ask Most About Motor Starter Wiring?<\/h2>\n<p><strong>Is 95\/96 always the overload trip contact?<\/strong> It is a common IEC convention, but the exact manual is the authority.<\/p>\n<p><strong>Can I replace a DOL starter with a VFD?<\/strong> Only after a system check. A VFD changes starting, speed and wiring; amps alone do not make it a drop-in replacement.<\/p>\n<p><strong>Can a PLC replace the start and stop buttons?<\/strong> It can handle normal logic, but emergency stop and safety must follow the risk assessment and local standards.<\/p>\n<h2>Ready to Match the Drawing to the Right Starter?<\/h2>\n<p>Read the drawing twice: power from supply to motor, then trace Stop, Start, hold contact and overload trip. Verify the exact terminal drawing, coil voltage and overload range.<\/p>\n<p>Send SIMPLYBUY the starter model, nameplate photo, control voltage and quantity, plus a drawing. Review the BOM through the <a href=\"https:\/\/www.simplybuyglobal.com\/fa\/contact\/\" rel=\"noopener noreferrer\" target=\"_blank\">\u0635\u0641\u062d\u0647 \u062a\u0645\u0627\u0633<\/a>.<\/p>\n<p><em>Byline: JIANGFAN Q., Manager, Industrial Control and Electrical Products.<\/em><\/p>\n<hr\/>\n<p>status: draft<\/p>\n<p><img loading=\"lazy\" decoding=\"async\" width=\"1600\" height=\"900\" alt=\"Two motor control components on a white surface: a Schneider Electric TeSys LC1D65A contactor and an ABB MS116 manual motor starter, with text Motor Starter Wiring and Power and control components at left.\" class=\"wp-image-8968\" src=\"https:\/\/www.simplybuyglobal.com\/wp-content\/uploads\/2026\/10\/cover-5.webp\" srcset=\"https:\/\/www.simplybuyglobal.com\/wp-content\/uploads\/2026\/10\/cover-5.webp 1600w, https:\/\/www.simplybuyglobal.com\/wp-content\/uploads\/2026\/10\/cover-5-500x281.webp 500w, https:\/\/www.simplybuyglobal.com\/wp-content\/uploads\/2026\/10\/cover-5-1200x675.webp 1200w, https:\/\/www.simplybuyglobal.com\/wp-content\/uploads\/2026\/10\/cover-5-300x169.webp 300w, https:\/\/www.simplybuyglobal.com\/wp-content\/uploads\/2026\/10\/cover-5-768x432.webp 768w, https:\/\/www.simplybuyglobal.com\/wp-content\/uploads\/2026\/10\/cover-5-1536x864.webp 1536w, https:\/\/www.simplybuyglobal.com\/wp-content\/uploads\/2026\/10\/cover-5-18x10.webp 18w, https:\/\/www.simplybuyglobal.com\/wp-content\/uploads\/2026\/10\/cover-5-133x75.webp 133w, https:\/\/www.simplybuyglobal.com\/wp-content\/uploads\/2026\/10\/cover-5-960x540.webp 960w, https:\/\/www.simplybuyglobal.com\/wp-content\/uploads\/2026\/10\/cover-5-480x270.webp 480w, https:\/\/www.simplybuyglobal.com\/wp-content\/uploads\/2026\/10\/cover-5-800x450.webp 800w\" sizes=\"auto, (max-width:767px) 480px, (max-width:1600px) 100vw, 1600px\" \/><\/p>\n\n\n<div data-wp-draft-contact=\"1\" style=\"text-align: center; width: 100%;\"><a data-wp-card-role=\"contact-button\" href=\"https:\/\/www.simplybuyglobal.com\/fa\/contact\/\" rel=\"noopener noreferrer\" style=\"display: inline-flex;            align-items: center;            justify-content: center;            padding: 18px 27px;            min-height: 60px;            box-sizing: border-box;            background-color: #0C2B75;            color: #FFFFFF;            font-size: 16px;            font-weight: 500;            font-family: Arial, sans-serif;            text-decoration: none;            text-align: center;            border-radius: 50px;            line-height: 1.2;\" target=\"_blank\">\u062a\u0645\u0627\u0633 \u0628\u0627 \u0645\u0627<\/a><\/div>","protected":false},"excerpt":{"rendered":"<p>Quick Answer: A three-phase motor starter wiring diagram shows two circuits. The power circuit takes L1, L2 and L3 through a contactor and overload relay to<span class=\"excerpt-hellip\"> [\u2026]<\/span><\/p>\n","protected":false},"author":1,"featured_media":8968,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"footnotes":""},"categories":[154],"tags":[135],"class_list":["post-8971","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-motor-starter","tag-siemens"],"_links":{"self":[{"href":"https:\/\/www.simplybuyglobal.com\/fa\/wp-json\/wp\/v2\/posts\/8971","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.simplybuyglobal.com\/fa\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/www.simplybuyglobal.com\/fa\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/www.simplybuyglobal.com\/fa\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/www.simplybuyglobal.com\/fa\/wp-json\/wp\/v2\/comments?post=8971"}],"version-history":[{"count":1,"href":"https:\/\/www.simplybuyglobal.com\/fa\/wp-json\/wp\/v2\/posts\/8971\/revisions"}],"predecessor-version":[{"id":9127,"href":"https:\/\/www.simplybuyglobal.com\/fa\/wp-json\/wp\/v2\/posts\/8971\/revisions\/9127"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/www.simplybuyglobal.com\/fa\/wp-json\/wp\/v2\/media\/8968"}],"wp:attachment":[{"href":"https:\/\/www.simplybuyglobal.com\/fa\/wp-json\/wp\/v2\/media?parent=8971"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/www.simplybuyglobal.com\/fa\/wp-json\/wp\/v2\/categories?post=8971"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/www.simplybuyglobal.com\/fa\/wp-json\/wp\/v2\/tags?post=8971"}],"curies":[{"name":"\u0648\u0631\u062f\u067e\u0631\u0633","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}